DEE-24106 Electric power systems Voltage control

1. Let us assume that the resistance of the studied transmission line is 02. Theoretical maxi-
mum power flow through the line is achieved when the angle difference between line ends is
8 = 90% and voltage in both ends is constant 1.0 pu. Maximum power flow is Pmax = 1.0 pu.
a) Prove that reactive power losses in the line are 2.0 pu.

 

b) Prove that voltage in the middle of line is = pu.

2. Figure 1 represents 300 km long transmission line where voltage on both ends is Unv=U2y=
400 kV and power flow through line is P = 700 MW. Calculate how large series capacitor
needs to be connected in the middle of the line in order to have 0:=07= 0. Parameters of the
line are x = 0.33 O/km, b = 3.57 uS/km.

= o P O&(»

U, v i T Un

Figure 1.

3. Generator produces P = 80 MW active- and O = 0 reactive power. Connection point voltage
on the high voltage side of the transformer is U= 115 kV and network short-circuit power is
Sc = 1000 MVA when voltage is 115 kV. How much the connection point voltage will
change if a reactor (Un = 120 kV, On = 60 Mvar) is connected to same point?

M PO

      
   

G: Sy = 100 MVA
Un = 10,5 kV
Xg= 15

r M: SN = 100 MVA

110/10,5 kV

2 = 10% x

Figure 2.

4. A Generator (300 MVA, 23 kV) is feeding power through a transformer (330 MVA, 23/230
kV, A-Y connected, taps on A-side, leakage reactance 11 %) to a load (240 MVA, power
factor 0.9jna, 230 kV). The generator is maintaining the voltage on the high voltage side of
the transformer at nominal.

a) Determine generator active and reactive power when transformer ratio is 1:1/30*
b) Determine generator active and reactive power when transformer ratio is 1:1.05/30*


We use cookies

This website uses cookies, including third-party cookies, only for necessary purposes such as saving settings on the user's device, keeping track of user sessions and for providing the services included on the website. This website also collects other data, such as the IP address of the user and the type of web browser used. This information is collected to ensure the operation and security of the website. The collected information can also be used by third parties to enable the ordinary operation of the website.