EE.EES.420 Electric Power Quality - 24.01.2023

Exam text content

The text is generated with Optical Image Recognition from the original exam file and it can therefore contain erroneus or incomplete information. For example, mathematical symbols cannot be rendered correctly. The text is mainly used for generating search results.

Original exam
Tampere University Exam 24,1.2023
EE.EES.420 Electric Power Quality

Pertti Pakonen Programmable calculator allowed 4 questions/ 4 6 p

1. What causes fundamental frequency reactive power to occur in distribution networks, what are
the consequences of it and how it can be compensated? Give an example of a feasible application
for each compensation method. ‘

2. What is flicker and what causes it? Why flicker is harmful and how the intensity of flicker may
be evaluated? What characteristics of the source of flicker and the network affect the intensity
of flicker? Explain the aspects related to the management of flicker from the viewpoint of a
distribution system operator (DSO).

3. a) Why shunt-connected active power filter (APF) is connected close to the load? What are the
advantages and disadvantages of a series-connected APF compared to a shunt-connected APF?

b) What are resonances in electric power networks and how the resonant circuit may be formed?
What does resonance frequency mean and why is it relevant? What are the consequences of a
resonance and how the risk of a resonance may be mitigated?

4. Consider a three phase short circuit occurring on one feeder of a radially operated 20 kV
distribution network supplied by a 110 kV network. The total resistance and reactance of the
supplying 110 kV network and the 110 /20 kV main transformer together, transformed to the 20
kV voltage level, are 0.8 ohm and 4 ohm, respectively. The feeder resistance is 0.34 ohm/km
and the reactance 0.38 ohm/kin. The phase-to-phase voltages in the 20 kV network before the
fault are 21 kV.

a. draw the three phase and single line equivalent circuits of the fault case

b. explain why and how the voltages in the network change due to the fault

c. based on calculus, illustrate graphically the dependence of the feeder short circuit
current and the substation 20 kV busbar phase-to-phase voltage during the fault on the
fault location

d. explain shortly how the changes in voltage would be different and have to be
calculated differently if the fault was a two-phase short circuit

1d)


We use cookies

This website uses cookies, including third-party cookies, only for necessary purposes such as saving settings on the user's device, keeping track of user sessions and for providing the services included on the website. This website also collects other data, such as the IP address of the user and the type of web browser used. This information is collected to ensure the operation and security of the website. The collected information can also be used by third parties to enable the ordinary operation of the website.